PADMOUNT
TRANSFORMERS
Made with grain oriented magnetic laminations cut at 45° and assembled with the step lap method.
INSULATING OIL
Filled with PCB-free oil that has been dried and degassed, and complies with IEC standards.
WINDINGS
Made with oval or circular cross-section, with pure cellulose paper or double enamel conductor insulation.
TANK
Made in-house, either corrugated or with radiators made from stamped cold-rolled steel.
APPLICATIONS
The pad-mounted transformer, or base-mounted transformer, is a distribution transformer installed on the ground, equipped with a housing that contains the oil-filled active part, with the transformer terminals on the front side housed in an adjacent cabinet built to NEMA standards, equipped with a medium/low-voltage separator and lockable doors. The top of the enclosure is fitted with a cover that can only be removed from inside the cabinet itself.
Pad-mounted transformers are equipped with fuses consisting of a bayonet-mounted fuse located in the medium-voltage compartment, with a high-energy current-limiting backup fuse in series to protect against secondary faults and transformer overload. The bayonet-mounted fuse protects against secondary faults and transformer overload and is a field-replaceable device. The current-limiting backup fuse operates only in the event of a transformer fault; therefore, it is not field-replaceable.
Since all live connection points are securely enclosed in a grounded metal enclosure, a pad-mount transformer can be installed in residential areas, near sidewalks, and without any protective fencing.
These transformers are designed in accordance with the IEEE C57.12.34 or CSA C227.4 standards, which define performance, enclosure integrity, switching configurations, and testing procedures.
GBE pad-mounted transformers have rated power up to 5000 kVA or more, with primary voltage up to 35 kV and secondary voltage up to 600 volts.